Class ABB_ACS880_1Fo
|
Redaktör |
je |
|
Version |
1.0 |
|
Modified |
24-JUN-2013 11:11:13.86 |
|
Kod |
PlcTemplate |
|
Plc function object to profibus ABB_ACS880_1, powerlink ABB_ACS880_Epl_1 and
profinet ABB_ACS880_Pn_1.
Connect the function object to an object of class or subclass of
profibus class ABB_ACS880_1, powerlink class ABB_ACS880_Epl_1 or
profinet class ABB_ACS880_Pn_1.
See also
RtBody attributes pwr_sClass_ABB_ACS880_1Fo |
Boolean |
PowerOn |
pwo |
Should be true when the converter is energized. |
Boolean |
Start |
sta |
Start command. Bit 0 in control word is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
This bit is used togheter with bit 3 "Enable" in the controlword
to control start/stop commands.
|
Float32 |
RefSpeed |
REF |
Speed reference to the converter. |
Boolean |
NoOff2 |
nof2 |
OFF2 control. Bit 1 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
Default value is 1.
|
Boolean |
NoOff3 |
nof3 |
OFF3 control. Bit 2 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
Default value is 1.
|
Boolean |
EnableOperation |
eno |
Enable control. Bit 3 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
This bit is used togheter with bit 0 in the controlword to control
start/stop commands.
|
Boolean |
RampOutZero |
roz |
Ramp Out Zero. Bit 4 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
Default value is 1.
|
Boolean |
RampHold |
rh |
Ramp Out hold. Bit 5 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
Default value is 1.
|
Boolean |
RampInZero |
riz |
Ramp In Zero. Bit 6 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
Default value is 1.
|
AttrRef |
PlcConnect |
|
Connected ABB_ACS880_1 object in plant hierarchy. |
Boolean |
ReadyRemote |
rdy |
Ready remote is true when alla condition is Ok i.e.
start command is possible from this object. |
Boolean |
Run |
run |
Converter is started. |
Boolean |
Di1 |
di1 |
Status from converter IO digital input Di1. |
Boolean |
Di2 |
di2 |
Status from converter IO digital input Di2. |
Boolean |
Di3 |
di3 |
Status from converter IO digital input Di3. |
Boolean |
Di4 |
di4 |
Status from converter IO digital input Di4. |
Boolean |
Di5 |
di5 |
Status from converter IO digital input Di5. |
Boolean |
Di6 |
di6 |
Status from converter IO digital input Di6. |
Boolean |
DiIL |
diil |
Status from converter IO digital input DIIL. |
Boolean |
Sto |
sto |
True when converter STO function is activated.
Two digital input In1 and In2 affect this
safe torque off function. |
GraphPlcNode |
object_type |
11 |
parameters[0] |
9 |
parameters[1] |
1 |
parameters[2] |
10 |
parameters[3] |
0 |
subwindows |
1 |
subwindow_class[0] |
pwrb:Class-WindowPlc |
graphmethod |
0 (standard, individual attributes) |
graphindex |
0 |
default_mask[0] |
39 |
default_mask[1] |
3 |
segname_annotation |
1 |
compmethod |
58 |
compindex |
0 |
tracemethod |
0 |
traceindex |
0 |
connectmethod |
10 |
executeordermethod |
2 |
objname |
ABB_ACS880_1Fo |
graphname |
ABB_ACS880_1Fo |
Template Object |
NoOff2 |
1 |
NoOff3 |
1 |
RampOutZero |
1 |
RampHold |
1 |
RampInZero |
1 |
Attributes detail
Should be true when the converter is energized.
Start command. Bit 0 in control word is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
This bit is used togheter with bit 3 "Enable" in the controlword
to control start/stop commands.
Speed reference to the converter.
OFF2 control. Bit 1 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
Default value is 1.
OFF3 control. Bit 2 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
Default value is 1.
Enable control. Bit 3 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
This bit is used togheter with bit 0 in the controlword to control
start/stop commands.
Ramp Out Zero. Bit 4 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
Default value is 1.
Ramp Out hold. Bit 5 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
Default value is 1.
Ramp In Zero. Bit 6 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW
Default value is 1.
Connected ABB_ACS880_1 object in plant hierarchy.
Ready remote is true when alla condition is Ok i.e.
start command is possible from this object.
Status from converter IO digital input Di1.
Status from converter IO digital input Di2.
Status from converter IO digital input Di3.
Status from converter IO digital input Di4.
Status from converter IO digital input Di5.
Status from converter IO digital input Di6.
Status from converter IO digital input DIIL.
True when converter STO function is activated.
Two digital input In1 and In2 affect this
safe torque off function.