Class ABB_ACS880_1Fo
Author je
Version 1.0
Modified 24-JUN-2013 11:11:13.86
Code PlcTemplate
 Plc function object to profibus ABB_ACS880_1, powerlink ABB_ACS880_Epl_1 and
 profinet ABB_ACS880_Pn_1.


 Connect the function object to an object of class or subclass of
 profibus class ABB_ACS880_1, powerlink class ABB_ACS880_Epl_1 or
 profinet class ABB_ACS880_Pn_1.

See also



RtBody attributes pwr_sClass_ABB_ACS880_1Fo
Boolean PowerOn pwo Should be true when the converter is energized.
Boolean Start sta Start command. Bit 0 in control word is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW

This bit is used togheter with bit 3 "Enable" in the controlword
to control start/stop commands.
Float32 RefSpeed REF Speed reference to the converter.
Boolean NoOff2 nof2 OFF2 control. Bit 1 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW

Default value is 1.
Boolean NoOff3 nof3 OFF3 control. Bit 2 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW

Default value is 1.
Boolean EnableOperation eno Enable control. Bit 3 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW

This bit is used togheter with bit 0 in the controlword to control
start/stop commands.
Boolean RampOutZero roz Ramp Out Zero. Bit 4 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW

Default value is 1.
Boolean RampHold rh Ramp Out hold. Bit 5 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW

Default value is 1.
Boolean RampInZero riz Ramp In Zero. Bit 6 in controlword is set to true.
See class help for object ABB_ACS880_1 attribute MainControlCW

Default value is 1.
AttrRef PlcConnect   Connected ABB_ACS880_1 object in plant hierarchy.
Boolean ReadyRemote rdy Ready remote is true when alla condition is Ok i.e.
start command is possible from this object.
Boolean Run run Converter is started.
Boolean Di1 di1 Status from converter IO digital input Di1.
Boolean Di2 di2 Status from converter IO digital input Di2.
Boolean Di3 di3 Status from converter IO digital input Di3.
Boolean Di4 di4 Status from converter IO digital input Di4.
Boolean Di5 di5 Status from converter IO digital input Di5.
Boolean Di6 di6 Status from converter IO digital input Di6.
Boolean DiIL diil Status from converter IO digital input DIIL.
Boolean Sto sto True when converter STO function is activated.
Two digital input In1 and In2 affect this
safe torque off function.

DevBody attributes 
pwrs:Class-$PlcNode PlcNode  


GraphPlcNode
object_type 11
parameters[0] 9
parameters[1] 1
parameters[2] 10
parameters[3] 0
subwindows 1
subwindow_class[0] pwrb:Class-WindowPlc
graphmethod 0 (standard, individual attributes)
graphindex 0
default_mask[0] 39
default_mask[1] 3
segname_annotation 1
compmethod 58
compindex 0
tracemethod 0
traceindex 0
connectmethod 10
executeordermethod 2
objname ABB_ACS880_1Fo
graphname ABB_ACS880_1Fo


Template Object
NoOff2 1
NoOff3 1
RampOutZero 1
RampHold 1
RampInZero 1


Attributes detail


PowerOn Input
Class Input
Type Boolean
Flags Noinvert
GraphName pwo
Body RtBody
 Should be true when the converter is energized.

Start Input
Class Input
Type Boolean
Flags Noinvert
GraphName sta
Body RtBody
 Start command. Bit 0 in control word is set to true.
 See class help for object ABB_ACS880_1 attribute MainControlCW

 This bit is used togheter with bit 3 "Enable" in the controlword
 to control start/stop commands.


RefSpeed Input
Class Input
Type Float32
Flags Noinvert
GraphName REF
Body RtBody
   Speed reference to the converter.

NoOff2 Input
Class Input
Type Boolean
Flags Noinvert
GraphName nof2
Body RtBody
 OFF2 control. Bit 1 in controlword is set to true.
 See class help for object ABB_ACS880_1 attribute MainControlCW

 Default value is 1.


NoOff3 Input
Class Input
Type Boolean
Flags Noinvert
GraphName nof3
Body RtBody
 OFF3 control. Bit 2 in controlword is set to true.
 See class help for object ABB_ACS880_1 attribute MainControlCW

 Default value is 1.


EnableOperation Input
Class Input
Type Boolean
Flags Noinvert
GraphName eno
Body RtBody
 Enable control. Bit 3 in controlword is set to true.
 See class help for object ABB_ACS880_1 attribute MainControlCW

 This bit is used togheter with bit 0 in the controlword to control
 start/stop commands.


RampOutZero Input
Class Input
Type Boolean
Flags Noinvert
GraphName roz
Body RtBody
 Ramp Out Zero. Bit 4 in controlword is set to true.
 See class help for object ABB_ACS880_1 attribute MainControlCW

 Default value is 1.


RampHold Input
Class Input
Type Boolean
Flags Noinvert
GraphName rh
Body RtBody
 Ramp Out hold. Bit 5 in controlword is set to true.
 See class help for object ABB_ACS880_1 attribute MainControlCW

 Default value is 1.


RampInZero Input
Class Input
Type Boolean
Flags Noinvert
GraphName riz
Body RtBody
 Ramp In Zero. Bit 6 in controlword is set to true.
 See class help for object ABB_ACS880_1 attribute MainControlCW

 Default value is 1.


PlcConnect Intern
Class Intern
Type AttrRef
Flags
Body RtBody
   Connected ABB_ACS880_1 object in plant hierarchy.

ReadyRemote Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName rdy
Body RtBody
 Ready remote is true when alla condition is Ok i.e.
 start command is possible from this object.

Run Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName run
Body RtBody
 Converter is started.

Di1 Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName di1
Body RtBody
 Status from converter IO digital input Di1.

Di2 Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName di2
Body RtBody
 Status from converter IO digital input Di2.

Di3 Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName di3
Body RtBody
 Status from converter IO digital input Di3.

Di4 Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName di4
Body RtBody
 Status from converter IO digital input Di4.

Di5 Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName di5
Body RtBody
 Status from converter IO digital input Di5.

Di6 Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName di6
Body RtBody
 Status from converter IO digital input Di6.

DiIL Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName diil
Body RtBody
 Status from converter IO digital input DIIL.

Sto Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName sto
Body RtBody
 True when converter STO function is activated.
 Two digital input In1 and In2 affect this
 safe torque off function.

PlcNode Buffer
Class Buffer
Type pwrs:Class-$PlcNode
Flags
Body DevBody